Skip to content

kVA Calculator

Enter kVA, kW, amps or motor horsepower and get the other three, for single-phase or three-phase at any voltage — plus the generator size that actually covers the load.

Where are you?

AWG, NEC, 120/240 V, miles and gallons — we remember this on every calculator.

What do you already know?
Apparent power

The kVA figure on a generator or transformer nameplate. It is the number manufacturers advertise, because it is the larger one.

kVA
Supply
Supply voltage

On three-phase this is the line-to-line voltage — 208, 240 or 480 in North America, 400 across most of Europe. It is never the 120 V or 230 V you measure to neutral.

V
Power factor

The fraction of the current that does useful work. Generator and transformer nameplates assume 0.8. A resistive load such as a heater is 1.0.

0.8
Generator / transformer nameplate
0.80
Mixed commercial load
0.85–0.90
Induction motor at full load
0.85
Induction motor lightly loaded
0.60–0.70
Heating, resistive only
1.00
Motor efficiency

How much of the electrical input reaches the shaft. Used in both directions — it is what turns kilowatts into a horsepower rating and back. Small motors are around 0.80; IE3 premium-efficiency motors above 10 HP reach 0.92 or better.

0.88
Under 1 HP
0.72–0.80
1–10 HP
0.84–0.89
10–100 HP, IE3
0.91–0.95

Your result

Apparent power

10 kVA

Real power
8 kW
Current per line
12 A
Motor equivalent
9.44 HP
Reactive power
6 kVAR
Supply
480 V 3-phase
Generator size
12.5 kVA

🪿 The goose says: 10 kVA at power factor 0.80 is 8 kW, drawing 12 A per line from a 480 V three-phase supply. A generator for it wants to be 12.5 kVA.

  • At a power factor of 0.80, 10 kVA delivers 8 kW. The missing 6 kVAR is reactive power — it flows back and forth without doing work, but your cable and your alternator still have to carry it.
  • Three-phase: kVA = √3 × 480 V × 12 A ÷ 1000. Each line carries 12 A. Using 480 V with the single-phase formula would understate the load by 73%.
  • A generator for this load wants 12.5 kVA — 25% above the calculated demand, so the set is not running flat out. North American sets are usually advertised in kW instead, which for this size is about 10 kW.

kVA to kW at other power factors

What 10 kVA actually delivers as the load changes character. This is the conversion people get wrong most often.

Power factor 0.60
6 kW lightly loaded motors
Power factor 0.70
7 kW lightly loaded motors
Power factor 0.80
8 kW nameplate convention
Power factor 0.85
8.50 kW mixed load
Power factor 0.90
9 kW mixed load
Power factor 1.00
10 kW pure heating

kW = kVA × power factor. There is no fixed conversion — quoting one without the other is meaningless.

The same load at other voltages

Apparent power stays the same; the current does not. This is what decides your cable size.

120 V single-phase
83.3 A
240 V single-phase
41.7 A
208 V three-phase
27.8 A
480 V three-phase
12 A your supply
600 V three-phase
9.62 A

Single-phase: A = kVA × 1000 ÷ V. Three-phase: A = kVA × 1000 ÷ (√3 × V).

How this generator kVA calculator works

kVA and kW measure the same load twice. kVA is apparent power — volts multiplied by amps, everything the supply has to carry. kW is real power — the part that actually turns a shaft or makes heat. The ratio between them is the power factor.

The difference exists because current in a coil lags behind voltage. That lagging portion still flows through your cable, your breaker and your alternator, heating all three, but it does no work and your meter does not bill you for it. Which is why a generator is rated in kVA and sold on kW, and why the two numbers on the same nameplate differ by exactly the 0.8 the industry assumes.

Horsepower brings in a second, unrelated loss. A motor nameplate quotes shaft output. Getting that output requires more electrical input, because no motor is perfectly efficient. So converting HP to kVA needs both corrections: divide by efficiency to get electrical kW, then divide by power factor to get kVA.

Three-phase is the third complication. All three lines carry current and the phases are 120 degrees apart, so with voltage measured line-to-line the power works out to √3 — about 1.732 — times line volts times line amps.

  1. Step 1 Apparent power, single-phase kVA = volts × amps ÷ 1000
  2. Step 2 Apparent power, three-phase kVA = √3 × line_volts × line_amps ÷ 1000 Line volts means 208, 240 or 480 — the voltage between two phases.
  3. Step 3 kVA to kW kW = kVA × power_factor
  4. Step 4 kW to kVA kVA = kW ÷ power_factor
  5. Step 5 Horsepower to kVA kVA = HP × 0.7457 ÷ efficiency ÷ power_factor Two divisions, two different losses. Efficiency is the motor; power factor is the supply.
  6. Step 6 Reactive power kVAR = √(kVA² − kW²) The three form a right triangle. Correcting power factor shrinks the kVAR side and pulls kVA down towards kW.
  7. Step 7 Generator sizing generator_kVA = load_kVA × 1.25, rounded up to a size you can buy Sized on kVA, not kW, because the alternator carries the reactive current too.

Example: a 10 HP motor at 88% efficiency and 0.85 power factor. Shaft output is 7.46 kW, electrical input is 8.47 kW, and apparent power is 9.97 kVA. On a 480 V three-phase supply that is 12.0 A per line. A generator to start and run it wants to be about 12.5 kVA before you allow for starting current, which for a direct-on-line motor can be six times higher again.

Assumptions & caveats

Everything this calculator quietly assumes on your behalf. If one of these does not match your situation, the answer will be off.

  • The load is assumed balanced across all three phases when three-phase is selected. An unbalanced load has to be worked out phase by phase, and the worst phase decides the cable.
  • Voltage entered for three-phase is line-to-line. Entering the line-to-neutral figure understates the load by a factor of 1.73.
  • Power factor is treated as a single constant. In reality it moves with load — an induction motor at a quarter load can fall to 0.5, which is a good reason not to oversize motors.
  • Motor efficiency applies only to the horsepower conversion. It is a nameplate figure at full load, and drops off sharply below about 40% load.
  • Starting current is not included. A direct-on-line induction motor draws six to eight times its running current for a few seconds, which is usually what sizes the generator rather than the running kVA.
  • Generator sizing here applies a flat 25% margin on apparent power. A real specification would also account for step-load acceptance, harmonic content from variable-speed drives, and altitude and temperature derating.
  • Horsepower means mechanical horsepower at 745.7 W. Some equipment quotes electrical or metric horsepower, both slightly different.

Frequently asked questions

How do I convert kVA to kW?

Multiply kVA by the power factor: kW = kVA × pf. At the standard 0.8 assumed on generator nameplates, a 10 kVA set delivers 8 kW. There is no fixed conversion factor — a purely resistive load at power factor 1.0 gets the full 10 kW from the same machine.

How many kW is a 10 kVA generator?

Eight kilowatts, at the 0.8 power factor generator manufacturers assume. That is the number to compare against a load calculation, not the 10 on the label. If a set is advertised at 10 kVA and 8 kW, those are the same machine described twice, not two ratings.

How do I convert HP to kVA?

Multiply horsepower by 0.7457 to get mechanical kilowatts, divide by the motor efficiency to get electrical kilowatts, then divide by the power factor to get kVA. A 10 HP motor at 88% efficiency and 0.85 power factor comes to about 10 kVA. Both divisions matter — skipping the efficiency step undersizes the supply by 10 to 20%.

What is the difference between kVA and kW?

kVA is apparent power, everything the supply carries; kW is real power, the part that does work. The gap is reactive current that flows back and forth through your cable without producing anything useful. Cables, breakers and generators are sized on kVA; your electricity meter bills you on kW.

How do I calculate three-phase kW?

Multiply √3 (1.732) by the line-to-line voltage, by the current in one line, by the power factor, then divide by 1,000. A 480 V supply at 40 A and 0.85 power factor gives 1.732 × 480 × 40 × 0.85 ÷ 1000 = 28.3 kW. The commonest mistake is entering the line-to-neutral voltage instead of line-to-line.

What size generator do I need for a 10 HP motor?

About 12.5 kVA to run it, but starting is what really decides the size. A direct-on-line induction motor draws six to eight times its running current for a few seconds, so a set sized only on running load will stall or trip. Soft starters and variable-frequency drives cut the inrush enough to bring the generator down a size or two.

Why is power factor 0.8 on generator nameplates?

It is a long-standing industry convention that reflects a typical mixed commercial load of motors, lighting and electronics. It also lets manufacturers print the larger kVA number on the front. If your load is genuinely resistive — heaters, ovens, filament lighting — you can draw the full kVA in kilowatts, but very few real installations are.