Skip to content

Wire Gauge Calculator

Enter amps, distance and voltage to get the cable size you need — checked against both voltage drop and ampacity, with resistance, the metric equivalent and parallel-run options worked out for you.

Where are you?

AWG, NEC, 120/240 V, miles and gallons — we remember this on every calculator.

Current the circuit will carry

For a device, use its rated amps. For a breaker-protected circuit, use the breaker size. Watts ÷ volts gives you amps if you only know watts.

A
One-way distance

Measure from the power source to the device, one direction only. The calculator doubles it, because current has to come back too. Round up and add a little slack for routing.

Distance unit
System voltage

The nominal voltage of the circuit. Low-voltage DC systems are far more sensitive to voltage drop, because the same lost volt is a much bigger share of the total.

Maximum acceptable voltage drop

3% is the usual design target and what NEC recommends for a branch circuit. Use 2% for anything sensitive — solar charging, LED lighting, long runs. 10% is only acceptable for non-critical automotive and marine loads, where ABYC and SAE practice allows it.

Conductors per leg

Running two or more wires side by side shares both the current and the voltage drop between them. It is the standard fix when a single conductor would be impractically thick — but see the safety note before doing it on a mains circuit.

Conductor material

Copper unless you know otherwise. Aluminum is cheaper for big feeders but needs roughly two sizes larger for the same job, plus anti-oxidant paste and aluminum-rated lugs.

Your result

Cable size you need (copper)

2 AWG

Voltage drop
0.29 V
Drop percentage
2.43%
Limited by
Voltage drop
Same size in mm²
33.6 mm²
Circuit resistance
0.01 Ω
Rating at 60°C
95 A

🪿 The goose says: Run 2 AWG copper — step up to 1 AWG if you want to stay under 2% drop.

  • Voltage drop is the binding constraint here. 10 AWG would carry 30 A safely, but you would lose too much voltage over 25 ft.

Estimate for planning only. Have any electrical work verified by a qualified electrician and installed to code — see the full disclaimer at the bottom of this page.

Running conductors in parallel

Splitting the run across more conductors divides both the current and the cross-section each one has to provide. Here is what 30 A over 25 ft needs at each option.

Single run
2 AWG 2.43% drop
2 in parallel
2 × 4 AWG equivalent to 1 AWG · 1.93% drop
3 in parallel
3 × 6 AWG equivalent to 1.3 AWG · 2.05% drop
4 in parallel
4 × 8 AWG equivalent to 2 AWG · 2.44% drop

NEC 310.10(H) only permits paralleled conductors at 1/0 AWG and larger, and they must be identical in material, size, length and termination. Below 1/0 this is a low-voltage DC technique — common in vans, boats and solar, and not code-compliant on an AC branch circuit.

How this wire gauge calculator works

Wire size is decided by two separate questions, and the answer is whichever one demands the thicker wire.

The first question is heat. Every conductor has an ampacity — the current it can carry continuously without its insulation cooking. That comes straight from the NEC table, and it does not care how long your run is.

The second is voltage drop. Copper has resistance, so some of your voltage is lost as heat on the way out and on the way back. Over 10 feet nobody notices. Over 80 feet at 12 volts, a fridge browns out. This is why long runs need thick wire even when the current is modest.

  1. Step 1 How many volts can you afford to lose? allowed_drop_V = system_voltage × drop_target% At 12V and 3%, that is only 0.36 V. At 240V and 3%, it is 7.2 V — which is why low-voltage runs need fat cable.
  2. Step 2 Convert that into circular mils of copper required_cmil = (2 × K × amps × one_way_feet) ÷ allowed_drop_V K is 12.9 for copper and 21.2 for aluminum. The 2 is there because current travels out and back.
  3. Step 3 Round up to a real wire size The next size in the AWG table whose circular mils meet or exceed the requirement
  4. Step 4 Now check heat The wire must also meet the NEC 60°C ampacity for your current A 100 ft, 5-amp run might be drop-limited at 10 AWG; a 3 ft, 60-amp run is ampacity-limited at 4 AWG.
  5. Step 5 Take the thicker of the two final_size = max(drop_result, ampacity_result)
  6. Step 6 Split it across parallel conductors if you want to per_conductor_cmil = required_cmil ÷ runs per_conductor_amps = amps ÷ runs Two equal conductors have twice the cross-section and half the resistance, which is exactly three AWG sizes — two 12 AWG behave like one 9 AWG.

Example: 30 A at 12V over 20 ft one-way, 3% drop. Allowed drop is 0.36 V, so required circular mils = (2 × 12.9 × 30 × 20) ÷ 0.36 = 43,000 — that is 3 AWG. Ampacity only needs 10 AWG. Voltage drop wins, so you run 3 AWG. Split across two conductors, each needs 21,500 circular mils, which is 6 AWG — and two 6 AWG really is equivalent to one 3 AWG.

Assumptions & caveats

Everything this calculator quietly assumes on your behalf. If one of these does not match your situation, the answer will be off.

  • Ampacity figures come from NEC Table 310.16, 60°C column. That is the conservative column and matches the terminal rating on most residential breakers and devices. Equipment rated for 75°C terminals may allow a smaller conductor — an electrician can confirm.
  • No ambient-temperature or conduit-fill derating is applied. More than three current-carrying conductors in one conduit, or an attic above 86°F, both reduce ampacity — sometimes by 30% or more.
  • The formula uses DC resistance. On AC circuits above roughly 1/0 AWG, inductive reactance adds a little more drop than shown, and the effect grows with conductor size.
  • Resistivity constants of 12.9 (copper) and 21.2 (aluminum) ohm-cmil/ft assume a conductor at about 75°C. Cold wire has slightly less resistance and less drop.
  • Distance is one-way. The calculator doubles it for the return path. Three-phase circuits use a different multiplier and are covered in the Europe & UK mode, not here.
  • NEC 240.4(D) caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper regardless of what any other table says.
  • Continuous loads — anything running more than three hours, like an EV charger — must be sized at 125% of the load current under NEC 210.19. Enter the already-adjusted figure if that applies to you.
  • 18 and 16 AWG appear here for low-power DC accessory wiring only; they are not NEC branch-circuit sizes.
  • Parallel conductors are assumed identical in material, size, length and termination, which is what makes the current divide evenly. NEC 310.10(H) only permits paralleling at 1/0 AWG and larger on AC circuits; below that it is a low-voltage DC technique used in vans, boats and battery banks.
  • Resistance figures use the same 12.9 and 21.2 ohm-circular-mil-per-foot constants as the voltage-drop calculation, which correspond to a conductor at roughly 75°C. At room temperature copper is about 8% lower.
  • The mm² equivalent shown is a direct area conversion, not a recommendation. The two systems use different ampacity tables, so a metric size that matches on cross-section may not be compliant for the same current.
  • A 10% drop target reflects ABYC and SAE practice for non-critical automotive and marine loads only. It is not acceptable for building wiring under any code.

Frequently asked questions

What gauge wire do I need for 30 amps?

For a 30-amp 120V or 240V circuit, 10 AWG copper is the NEC minimum, and that holds for runs up to roughly 50 feet. Past that, voltage drop takes over and you want 8 AWG. On a 12V system, 30 amps needs 3 or 4 AWG at anything over about 15 feet.

What gauge wire do I need for 50 amps?

A 50-amp circuit needs 6 AWG copper as a minimum on the 60°C column, or 8 AWG if all terminations are rated 75°C and an electrician signs off on it. For a 50-amp RV pedestal or a subpanel more than 60 feet away, step up to 4 AWG to hold voltage drop under 3%.

What wire size do I need for a 100 foot run?

It depends entirely on current and voltage, because a 100-foot run is where voltage drop, not heat, decides the answer. At 120V and 20 amps, 100 feet needs 8 AWG instead of the usual 12 AWG. At 12V, a 100-foot run of any real current needs cable so thick it is usually cheaper to move the battery.

What wire size do I need for 12V solar?

Panel-to-controller runs are usually 10 AWG for a few hundred watts, because panel voltage is higher and current is low. Controller-to-battery and battery-to-inverter runs are the thick ones: 4 AWG for 100 amps over a few feet, 2/0 for a 3,000 W inverter. Keep the battery and inverter as close together as you physically can.

Copper or aluminum wire — which should I use?

Copper for almost everything: it carries more current per size, terminates reliably, and is what most household devices are rated for. Aluminum makes sense for long, heavy feeders — a 200-amp service or a run to a detached garage — where the material cost saving is real. Aluminum needs about two sizes larger, AL-rated connectors and anti-oxidant paste.

What happens if the wire gauge is too small?

Two things, and the second one is the dangerous one. Voltage sags, so motors run hot, lights dim and chargers take longer. And the wire itself heats up, which over time degrades the insulation and can start a fire inside a wall — which is why ampacity is a code requirement, not a suggestion.

What is two 12 AWG wires in parallel equal to?

About 9 AWG — doubling any conductor gains exactly three gauge sizes, because two equal wires have twice the cross-section and half the resistance. Two 6 AWG make 3 AWG, two 1/0 make 3/0, and three in parallel gains about five sizes. NEC 310.10(H) only permits this at 1/0 and larger on AC circuits, though it is common practice on low-voltage DC.

Can I run two wires in parallel instead of one thick one?

Electrically yes, and it is the standard fix when a single conductor would be impractically stiff — a 4/0 battery cable is hard to route, two 1/0 are not. All the conductors must be the same material, size, length and termination, or the current will not divide evenly. On AC branch circuits NEC restricts this to 1/0 and larger; on 12 V DC in a van or boat it is routine.

What is the resistance of 12 AWG wire?

About 1.98 ohms per 1,000 feet of copper at operating temperature, or 0.0065 ohms per foot. Each gauge size up roughly multiplies resistance by 1.26, so 14 AWG is about 3.1 ohms per 1,000 ft and 10 AWG about 1.24. Resistance is what produces voltage drop, which is why long runs need thicker wire even at modest current.

How do I convert AWG to mm²?

Divide the circular-mil area by 1,973.5, or use the rough equivalents: 14 AWG is 2.1 mm², 12 AWG 3.3, 10 AWG 5.3, 8 AWG 8.4, 6 AWG 13.3, 4 AWG 21.2 and 1/0 is 53.5 mm². There is no clean one-to-one match, so always round up to the next standard metric size — and remember the two systems carry different ampacity ratings.

Can I use this for speaker wire?

No — speaker wire is sized by a different rule. Rather than a percentage of supply voltage, the target is keeping total wire resistance below about 5% of the speaker impedance, so an 8 ohm speaker wants under 0.4 ohms of cable. That usually means 16 AWG for short runs and 12 AWG past about 50 feet. The resistance figure here will help, but the drop percentage will not.

Does a longer wire run need thicker wire?

Yes. Resistance is proportional to length, so doubling the distance doubles the voltage lost. Ampacity does not change with length, but voltage drop does, and on long runs it is almost always the constraint that sets your wire size.

Safety disclaimer

This is an estimate for planning. Electrical work should be verified by a licensed electrician and installed per NEC and your local code. Derating for ambient temperature, conduit fill and continuous loads can all change the required size, and this calculator does not apply them.